10KW Inverter& EVI Air Source ( Ultra-Low Ambient Temp.) Heat Pump


SPECIFICATION







Product Model: DFN 10AAH- 10KW

ModelDFN10AAH - 10KW
Power Supply - Refrigerant220-240V/1PH/ 50Hz -R410A
Heating Capacity ( KW ) - A10
Rated Input Power ( KW ) - A2.6
COP ( W/W ) - A3.85
Heating Capacity ( KW ) - B7.4
Rated Input Power ( KW ) - B2.76
COP ( W/W ) - B2.68
Cooling Capacity ( KW ) - C8.3
Rated Input Power ( KW ) - C2.76
EER ( W/W ) - C3.01
Max. Input Power ( KW )3.4
Max. Input Current ( A )16
Compressor Highly or Mitsubishi EVI Technology Twin Rotary
FanDC inverter brushless fans
Fan Quantity1
Fan Airflow ( m3/h )3000
Fan Rated Power ( W )100
Heat exchangerHigh efficiency plate type heat exchanger
WaterSide Pressure Drop ( Kpa )22
Inlet/Outlet Pipe Size ( mm )DN25
Min. Water Flow ( m3/H )>1.6
Noise ( dB(A) )≤56
Heating Water Temp. ℃20 ~ 60℃
Cooling Water Temp. ℃5 ~ 20 ℃
Operating Ambient Temp. ℃ -35°C~45℃
Unit Dimension ( mm )1100*400*850
Weight ( KG )72/80
Performance Condition - A : Ambient temp. (DB/WB): 7°C/6°C, Water temp. (In/Out): 40°C/ 45°C;
Performance Condition - B : Ambient temp. (DB/WB): -12°C/-14°C, Water temp. (Out): 41°C
Performance Condition - C: Ambient temp. (DB/WB): 35°C/24°C, Water temp. (In/Out): 12°C/7°C.


Copyright@ Changzhou City Definuo Electrical Co.,Ltd.   , Powered by 腾云建站仅向商家提供技术服务 .